CA2SK20G7 - Schneider Electric - Square D Control Relay

 

GENERAL SPECIFICATIONS

Main
Range TeSys
product name TeSys CASK
Product or Component Type Control relay
Device short name CA2SK
Contactor application Control circuit
Utilisation category DC-13
AC-15
Pole contact composition 2 NO
[Ue] rated operational voltage <= 690 V <= 400 Hz
Control circuit type AC 50/60 Hz
[Uc] control circuit voltage 120 V AC 50/60 Hz
Complementary
[Ith] conventional free air thermal current 10 A (at 131 °F (55 °C))
Associated fuse rating 10 A gL conforming to VDE 0660
10 A gL conforming to IEC 60947
[Ui] rated insulation voltage 690 V IEC 60947
690 V VDE 0110 group C
690 V BS 5424
690 V UL 508
690 V CSA C22.2 No 14
Mounting Support Rail
Plate
Connections - terminals screw clamp terminals 1 0.002…0.009 in² (1.5…6 mm²)solid
screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid
screw clamp terminals 1 0.0008…0.009 in² (0.5…6 mm²)flexible without cable end
screw clamp terminals 1 0.0005…0.009 in² (0.35…6 mm²)flexible with cable end
screw clamp terminals 2 0.0005…0.002 in² (0.35…1.5 mm²)flexible with cable end
screw clamp terminals 2 0.0005…0.004 in² (0.35…2.5 mm²)flexible without cable end
Tightening torque 7.08 lbf.in (0.8 N.m) screw clamp terminals pozidriv No 1
Control circuit voltage limits Drop-out: 0.2...0.75 Uc (at <122 °F (50 °C))
Operational: 0.85...1.1 Uc (at <122 °F (50 °C))
Operating time 6...8 ms coil de-energisation and NO opening
7...14 ms coil energisation and NO closing
8...10 ms coil de-energisation and NC closing
8...16 ms coil energisation and NC opening
Mechanical durability 10 Mcycles
Maximum operating rate 1200 cyc/h
Inrush power in VA 16 VA (at 68 °F (20 °C))
Hold-in power consumption in VA 4.2 VA (at 68 °F (20 °C))
Heat dissipation 1.4 W
Height 2.2 in (56 mm)
Width 1.06 in (27 mm)
Depth 2.2 in (55.5 mm)
Net Weight 0.291 lb(US) (0.132 kg)
Environment
Standards EN/IEC 60947-5-1
UL 60947-5-1
CSA C22.2 No 60947-5-1
IEC 60335-2-40:Annex JJ
UL 60335-2-40:Annex JJ
Product Certifications CB Scheme
cULus
EAC
CE
UKCA
IP degree of protection IP2X
Protective treatment TC IEC 60068
Ambient air temperature for operation -4…122 °F (-20…50 °C)
Ambient Air Temperature for Storage -58…158 °F (-50…70 °C)
Operating altitude 6561.68 ft (2000 m) without derating
Ordering and shipping details
Category US10I1222371
Discount Schedule 0I12
GTIN 3389110564174
Returnability Yes
Country of origin CZ
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 1.30 in (3.300 cm)
Package 1 Width 2.64 in (6.700 cm)
Package 1 Length 2.32 in (5.900 cm)
Package 1 Weight 4.480 oz (127.000 g)
Unit Type of Package 2 S01
Number of Units in Package 2 40
Package 2 Height 5.91 in (15.000 cm)
Package 2 Width 5.91 in (15.000 cm)
Package 2 Length 15.75 in (40.000 cm)
Package 2 Weight 11.530 lb(US) (5.230 kg)


PRODUCT DATASHEET

Schneider Electric_TeSys-Deca-K-and-SK-Control-Relays_CA2SK20G7