LC1D40008F7 - Square D - IEC contactor, TeSys Deca, 60A resistive, 4-Pole, 2 NO and 2

Square DSKU: SQDLC1D40008F7

Price:
Sale price$398.44
Stock:
Sold out

We source most out-of-stock items - request a fast quote.

Description

Main
Range TeSys
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Resistive load
Utilisation category AC-1
Poles description 4P
[Ue] rated operational voltage Power circuit <= 690 V AC 25...400 HzPower circuit <= 300 V DC
[Ie] rated operational current 60 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage 110 V AC 50/60 Hz
Complementary
Compatibility code LC1D
Pole contact composition 2 NO + 2 NC
Protective cover With
[Ith] conventional free air thermal current 60 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 320 A 104 °F (40 °C) - 10 s for power circuit720 A 104 °F (40 °C) - 1 s for power circuit72 A 104 °F (40 °C) - 10 min for power circuit165 A 104 °F (40 °C) - 1 min for power circuit
Associated fuse rating 80 A gG at <= 690 V coordination type 1 for power circuit80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole 5.4 W AC-1
[Ui] rated insulation voltage Power circuit 600 V CSAPower circuit 600 V ULPower circuit 690 V IEC 60947-4-1
Overvoltage category III
Pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 6 Mcycles
Electrical durability 1.4 Mcycles 60 A AC-1 <= 440 V
Control circuit type AC 50/60 Hz
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 50/60 Hz0.8...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 50 Hz0.85...1.1 Uc (-40…140 °F (-40…60 °C)):operational AC 60 Hz1...1.1 Uc (140…158 °F (60…70 °C)):operational AC 50/60 Hz
Inrush power in VA 140 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))160 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA 13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation 4…5 W at 50/60 Hz
Operating time 4...19 ms opening12...26 ms closing
Maximum operating rate 3600 cyc/h at 60 °C
Connections - terminals Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable endPower circuit: screw clamp terminals 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: solid without cable end
Tightening torque Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mmControl circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2Power circuit 70.8 lbf.in (8 N.m) screw clamp terminals 0.04…0.05 in² (25…35 mm²) hexagonal 0.2 in (4 mm)Power circuit 44.3 lbf.in (5 N.m) screw clamp terminals 0.002…0.04 in² (1…25 mm²) hexagonal 0.2 in (4 mm)Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Mounting Support PlateRail
Environment
Standards CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 60947-4-1
Product Certifications GLLROS (Lloyds register of shipping)GOSTULDNVRINACSACCCBV
IP degree of protection IP20 front face IEC 60529
Protective treatment THIEC 60068-2-30
Climatic withstand IACS E10 exposure to damp heat
Permissible ambient air temperature around the device -40…140 °F (-40…60 °C)140…158 °F (60…70 °C) with derating
Operating altitude 0...9842.52 ft (0...3000 m)
Fire resistance 1562 °F (850 °C) IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Shocks contactor open 8 Gn for 11 ms) Shocks contactor closed 10 Gn for 11 ms) Vibrations contactor opened 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz)
Height 5 in (127 mm)
Width 3.3 in (85 mm)
Depth 4.9 in (125 mm)
Product Weight 3.17 lb(US) (1.44 kg)
Ordering and shipping details
Category US1CTR121252
Discount Schedule CTR1
GTIN 3389110231588
Returnability Yes
Country of origin CZ
Packing Units
Unit Type of Package 1 PCE
Nbr. of units in pkg. 1
Package 1 Height 5.984 in (15.200 cm)
Package 1 Width 4.409 in (11.200 cm)
Package 1 Length 5.197 in (13.200 cm)
Package weight(Lbs) 3.206 lb(US) (1.454 kg)
Unit Type of Package 2 S02
Number of Units in Package 2 5
Package 2 Height 5.906 in (15.000 cm)
Package 2 Width 11.811 in (30.000 cm)
Package 2 Length 15.748 in (40.000 cm)
Package 2 Weight 16.854 lb(US) (7.645 kg)
Contractual warranty
Warranty (in months) 18
Product Datasheet
LC1D40008F7