Main
Range TeSys
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Resistive loadMotor control
Utilisation category AC-3AC-3eAC-4AC-1
Poles description 3P
[Ue] rated operational voltage Power circuit <= 300 V DC 25...400 HzPower circuit <= 690 V AC
[Ie] rated operational current 125 A (at <140 °F (60 °C)) at <= 1000 V AC AC-1 for power circuit80 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit80 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 230 V AC 50/60 Hz
Complementary
Motor power kW 22 kW at 220...230 V AC 50 Hz (AC-3)37 kW at 380...400 V AC 50 Hz (AC-3)45 kW at 415...440 V AC 50 Hz (AC-3)55 kW at 500 V AC 50 Hz (AC-3)45 kW at 660...690 V AC 50 Hz (AC-3)15 kW at 400 V AC 50 Hz (AC-4)22 kW at 220...230 V AC 50/60 Hz (AC-3e)37 kW at 380...400 V AC 50/60 Hz (AC-3e)45 kW at 415...440 V AC 50/60 Hz (AC-3e)55 kW at 500 V AC 50/60 Hz (AC-3e)45 kW at 660...690 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors15 hp at 230/240 V AC 50/60 Hz for 1 phase motors30 hp at 200/208 V AC 50/60 Hz for 3 phase motors30 hp at 230/240 V AC 50/60 Hz for 3 phase motors60 hp at 460/480 V AC 50/60 Hz for 3 phase motors60 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 10 A (at 140 °F (60 °C)) for signalling circuit125 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1250 A DC for signalling circuit conforming to IEC 60947-5-11100 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 640 A 104 °F (40 °C) - 10 s for power circuit990 A 104 °F (40 °C) - 1 s for power circuit135 A 104 °F (40 °C) - 10 min for power circuit320 A 104 °F (40 °C) - 1 min for power circuit100 A - 1 s for signalling circuit120 A - 500 ms for signalling circuit140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1200 A gG at <= 690 V coordination type 1 for power circuit160 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 0.8 mOhm - Ith 125 A 50 Hz for power circuit
Power dissipation per pole 5.1 W AC-312.5 W AC-15.1 W AC-3e
[Ui] rated insulation voltage Power circuit 600 V CSAPower circuit 600 V ULPower circuit 1000 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-1Signalling circuit 600 V CSASignalling circuit 600 V UL
Overvoltage category III
Pollution degree 3
[Uimp] rated impulse withstand voltage 8 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 4 Mcycles
Electrical durability 0.8 Mcycles 125 A AC-1 <= 440 V1.5 Mcycles 80 A AC-3 <= 440 V1.5 Mcycles 80 A AC-3e <= 440 V
Control circuit type AC 50/60 Hz standard
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.85...1.1 Uc (-40…131 °F (-40…55 °C)):operational AC 60 Hz0.3...0.6 Uc (-40…158 °F (-40…70 °C)):drop-out AC 50/60 Hz0.8...1.1 Uc (-40…131 °F (-40…55 °C)):operational AC 50 Hz1...1.1 Uc (131…158 °F (55…70 °C)):operational AC 50/60 Hz
Inrush power in VA 245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA 26 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))26 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation 6…10 W at 50/60 Hz
Operating time 20...35 ms closing6...20 ms opening
Maximum operating rate 3600 cyc/h at 60 °C
Connections - terminals Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable endPower circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: flexible without cable endPower circuit: connector 2 0.006…0.04 in² (4…25 mm²) - cable stiffness: flexible without cable endPower circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: flexible with cable endPower circuit: connector 2 0.006…0.02 in² (4…16 mm²) - cable stiffness: flexible with cable endPower circuit: connector 1 0.006…0.08 in² (4…50 mm²) - cable stiffness: solid without cable endPower circuit: connector 2 0.006…0.04 in² (4…25 mm²) - cable stiffness: solid without cable end
Tightening torque Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mmControl circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mmPower circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact1.5 ms on energisation between NC and NO contact
Mounting Support RailPlate
Environment
Standards EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1CSA C22.2 No 14UL 60947-4-1IEC 60335-2-40:Annex JJUL 60335-2-40:Annex JJIEC 60335-1:Clause 30.2
Product Certifications CCCULCB SchemeCSACEUKCAMarineEAC
IP degree of protection IP20 front face IEC 60529
Protective treatment THIEC 60068-2-30
Climatic withstand IACS E10 exposure to damp heat
Permissible ambient air temperature around the device -40…140 °F (-40…60 °C)140…158 °F (60…70 °C) with derating
Operating altitude 0...9842.52 ft (0...3000 m)
Fire resistance 1562 °F (850 °C) IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz) Shocks contactor open 8 Gn for 11 ms) Vibrations contactor closed 3 Gn, 5...300 Hz) Shocks contactor closed 10 Gn for 11 ms)
Height 5 in (127 mm)
Width 3.3 in (85 mm)
Depth 5.1 in (130 mm)
Product Weight 3.51 lb(US) (1.59 kg)
Ordering and shipping details
Category US1CTR121252
Discount Schedule CTR1
GTIN 3389110442823
Returnability Yes
Country of origin CZ
Packing Units
Unit Type of Package 1 PCE
Nbr. of units in pkg. 1
Package 1 Height 3.740 in (9.500 cm)
Package 1 Width 5.315 in (13.500 cm)
Package 1 Length 5.512 in (14.000 cm)
Package weight(Lbs) 3.452 lb(US) (1.566 kg)
Unit Type of Package 2 S02
Number of Units in Package 2 5
Package 2 Height 5.906 in (15.000 cm)
Package 2 Width 11.811 in (30.000 cm)
Package 2 Length 15.748 in (40.000 cm)
Package 2 Weight 17.624 lb(US) (7.994 kg)
Unit Type of Package 3 P06
Number of Units in Package 3 80
Package 3 Height 29.528 in (75.000 cm)
Package 3 Width 23.622 in (60.000 cm)
Package 3 Length 31.496 in (80.000 cm)
Package 3 Weight 301.910 lb(US) (136.944 kg)
Contractual warranty
Warranty (in months) 18
LC1 D80
a 85
b1 135
with LA4 DB3 or LAD 4BB3
with LA4 DF, DT 142
with LA4 DM, DW, DL 150
c 125
with cover, without add-on blocks 130
c1 150
with LAD N or C (2 or 4 contacts) 158
c2 170
c3 178
with LAD T, R, S and sealing cover 182